We manufacture this VCB perfectly according to ABB's VD4, besides its outside shape, its technical datas also meets ABBs requirements.
NO Item Unit Technical Date 1 Rated voltage KV 24 2 Rated insulating level Rated short time power frequency withstand voltage in 1min 1min 65 Raed lighting inpulse withstand voltage (peak value) 125 3 Rated Frequency HZ 50 4 Rated current A 630 630 1250 1250 1250 1600 2000 2500 5 Rated short circuit breaking current KA 20 25 31.5 6 Rated short time withstand current 20 25 31.5 7 Rated peak withstand current 50 63 80 8 4S rated short-time withstand current 4s 20 25 31.5 9 Rated shock steady current 50 63 80 10 Rated short-circuit closing current peak value 50 63 80 11 Duration of rated short-circuit current S 4 12 Mechanical life Times 20000(M2) 13 Rated making surge current of capacitor bank KA 12.5 The frequency is less than 1000Hz 14 Rated breaking current of single/symmetrical capacitor bank A 630/400 15 Breaking times at rated short-circuit current Times 274(E2) 16 Power frequency withstand voltage of secondary circuit V 2000 17 Rated operating voltage AC110/220 DC110/220 18 Rated operating order O-0.3s-CO-180s-CO 19 Energy storage times S less15 20 Contactor space mm 13 21 Contacting travel 4
23 Bounce time of Contactor during making ms less2 24 Different time of breaking / making of 3 phases less2 25 Average breaking speed m/s 1.1-1.7 26 Average making speed 0.6-1.1 27 Making time ms less 60 28 Brealing time less 45 29 Rebound amplitude of contact breaking 30 Permitted