Ningbo Mingde Electrical Science&Technology Co.,Ltd
|
|
| |
|
|
|
|

|

|
Click to enlarge image
|
Origin |
China |
Model Number |
VMD2 |
Brand Name |
Mingde |
| |
vacuum circuit breaker(VMD2) |
| |
VMD2 indoor vacuum circuit breaker is our independent research and developed high level 12 vacuum circuit breaker, its main features including main galvanic circle
installed in totally-enclosed three-phase insulating drums,and its operating mechanism gets simple construction, reliable movements, equipped with rich experience, and used in many high-end vacuum circuit breaker manufacturers.
Technical Parameters
| NO |
Item |
Unit |
Technical Date |
| 1 |
Rated voltage |
KV |
12 |
| 2 |
Rated insulating level |
Rated short time power frequency withstand voltage(1min) |
42 |
| Raed lighting inpulse withstand voltage (peak) |
75 |
| 3 |
Rated Frequency |
HZ |
50 |
| 4 |
Rated current |
A |
630 |
630 |
1250 |
1250 |
| 1250 |
1250 |
1600 |
1600 |
| |
2000 |
2000 |
| 2500 |
2500 |
| 3150 |
3150 |
| 4000 |
4000 |
| 5 |
Rated short circuit breaking current |
KA |
20 |
25 |
31.5 |
40 |
| 6 |
Rated short time withstand current |
20 |
25 |
31.5 |
40 |
| 7 |
Rated peak withstand current |
50 |
63 |
80 |
100 |
| 8 |
Rated short circuit breaking current(peak) |
50 |
63 |
80 |
100 |
| 9 |
4s thermal arrest current |
20 |
25 |
31.5 |
40 |
| 10 |
Rated Dynamic stability current |
50 |
63 |
80 |
100 |
| 11 |
|
|
|
|
|
|
|
|
|
| 12 |
Rated Condenser Banker Breaking Current |
A |
630/400 |
| 13 |
Rated Short circuit during time |
S |
4 |
| 14 |
Secondary circuit power frequency withstand voltage |
V |
2000 |
| 15 |
Rated operating voltage |
Making coil |
V |
AC110/220 DC110/220 |
| 16 |
Breaking coil |
AC110/220 DC110/221 |
| 17 |
Energy storing motor |
AC110/220 DC110/222 |
| 18 |
Breaking time (rated voltage) |
ms |
20-50 |
| 19 |
Making time (rated voltage) |
ms |
35-70 |
| 20 |
Energy storing time |
S |
≤15 |
| 21 |
Contact making jumping time |
ms |
≤2 |
| 22 |
Average breaking speed |
ms |
0.9-1.3 |
| 23 |
Average making speed |
ms |
0.4-0.8 |
| 24 |
Contact breaking rebound scope |
mm |
≤3 |
| 25 |
Main circuit resistence |
|
≤50(630A) |
| |
≤45(1250A) |
| |
≤35(1600-2000A) |
| |
≤25(Above2500A) |
| 26 |
Rated operating order |
|
O-0.3s-CO-180s-CO |
| |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|