General Profile
The VMD5 series medium voltage circuit breaker is our independent developed new generation 40.5 kv vacuuum circuit breaker. Its main characters as follows: the conductance circuit is installed in an three-phase insulating sleeve , its mechanism and conductance circuit adopts front and rear layout. And the mechanism is our deveoped new design, with simple construction, reliable operation All the technical parameters of breaker completely satisfy the Standards Of GB1984 AC Highvoltage Breaker, GB/T 11022 -1999 Common Specifications For High-Voltage Switchgear And Controlgear Standards, China Power Sector Standards DL403. Also meet the requirements of IEC62271-100, IEC56 and other main industrialized country’s similar standards It is universally used in power plant , electric network , metallurgy industry petrochemical industry and infrastructures,such as airport , subway, building. VMD5 circuit breaker possesses perfect mechanical and electric interlock equipment , meanwhile ,its high reliable operating performance and mechanical life , coodinated with matched switchgear cabinet ,to ensure normal power distribution , operator and equipment’s safety.
Technical Parameter
| NO |
Item |
Unit |
Technical Date |
| 1 |
Rated voltage |
KV |
40.5 |
| 2 |
Rated insulating level |
Rated short time power frequency withstand voltage(1min) |
95 |
| Raed lighting inpulse withstand voltage (peak value) |
185 |
| 3 |
Rated Frequency |
HZ |
50/60 |
| 4 |
Rated current |
A |
630 |
630 |
1250 |
| 1250 |
1250 |
1600 |
| ã |
2000 |
| 2500 |
| 5 |
Rated short circuit breaking current |
KA |
20 |
25 |
31.5 |
| 6 |
Rated short time withstand current |
20 |
25 |
31.5 |
| 7 |
Rated peak withstand current |
50 |
63 |
80 |
| 8 |
4S rated short-time withstand current |
20 |
25 |
31.5 |
| 9 |
Rated shock steady current |
50 |
63 |
80 |
| 10 |
Rated short-circuit closing current (peak value) |
50 |
63 |
80 |
| 11 |
Duration of rated short-circuit current |
S |
4 |
| 12 |
Mechanical life |
Times |
10000/30000/60000 |
| 13 |
Rated making surge current of capacitor bank |
KA |
12.5(The frequency is less than 1000Hz) |
| 14 |
Rated breaking current of single/symmetrical capacitor bank |
A |
630/400 |
| 15 |
Breaking times at rated short-circuit current |
Times |
20 |
| 16 |
Power frequency withstand voltage of secondary circuit |
V |
2000 |
| 17 |
Rated operating voltage |
AC110/220 |
DC110/220 |
| 18 |
Rated operating order |
ã |
O-0.3s-CO-180s-CO |
| 19 |
Energy storage times |
S |
≤15 |
| 20 |
Contactor space |
mm |
20± 2 |
| 21 |
Contacting travel |
6 ± 1 |
| 22 |
Phase clearance |
300 |
| 23 |
Bounce time of Contactor during making |
ms |
≤3 |
| 24 |
Different time of breaking / making of 3 phases |
≤2 |
| 25 |
Average breaking speed |
m/s |
1.5-1.9 |
| 26 |
Average making speed |
0.6-1.3 |
| 27 |
Making time |
ms |
30-80 |
| 28 |
Brealing time |
20-45 |
| 29 |
Rebound amplitude of contact breaking |
mm |
≤3 |
| 30 |
Permitted abrasion thickness of moving and fixed contacts |
3 |
| 31 |
Conductance circuit resistance |
µΩ |
Hndcart way |
Rated current |
| ≤45 |
less than 1250A |
| ≤35 |
1600-2000A |
| ≤25 |
less than 2500A |
| |
|
|
|
|
|
|
|
|
|
|
|
| The average breaking speed refers to the average speed of contactor’s first 12mm, and the average making speed is that of contactor’s last 12mm. |
|
|
|
|
| |
|
|
|
| |
|
|
|
|